Communication


Which interfaces can I use with the device?

Ethernet (Modbus/TCP) and RS-485 (Modbus RTU)

Click on the Ethernet A/B or RS-485 ports in the device overview.

Or

On the System tab, select the Communication configuration card.

Attention!

Material damage due to incorrect network settings!
Incorrect network settings can cause faults in the IT network.

  • Consult your network administrator for the correct network settings for your device.

images/download/attachments/251039198/Ethernet_%28ModbusTCP%29_and_RS-485_%28Modbus_RTU%29-version-1-modificationdate-1636637423000-api-v2.png


How do I configure the interfaces?

Step 1: Select interface

Select the interface.

images/download/attachments/251039198/Select_interface-version-1-modificationdate-1636637431000-api-v2.png


Step 2 (Option 1) : Ethernet (Modbus/TCP)

  • IPv4 configuration
    Select the type of address assignment for the Ethernet connection (TCP/IP):

DHCP (default setting)
On start-up, the device is automatically given an IP address, netmask and gateway by the DHCP server.

With this selection, only the hostname can be set.
All other parameters are preset.

Static IP address
Configure the communication interface parameters according to your own requirements. Use this mode for simple networks with no DHCP server.

  • IP address
    Setting only required if Fixed IP Address was selected for the address assignment.

  • Subnet mask
    Setting only required if Fixed IP Address was selected for the address assignment.

  • Standard gateway
    Setting only required if Fixed IP Address was selected for the address assignment.

  • DNS server
    Setting only required if Fixed IP Address was selected for the address assignment.

  • Hostname
    Assign a hostname for the system.


images/download/attachments/251039198/Ethernet_%28ModbusTCP%29-version-1-modificationdate-1636984191000-api-v2.png

Step 2 (Option 2): RS-485 (Modbus RTU)

  • Modbus mode

Modbus server (slave)
The device is created as a server in a bus structure.

Modbus client (gateway)
The device is the client of a bus structure.

  • Device ID

    Select a device address with which the device can be addressed in the bus structure.
    Each device address exists once in a bus structure!

    Setting range: 1.. 247 (according to Modbus standard)
    1 (default setting)

  • Baud rate

    Select a uniform baud rate for all devices in the bus structure!

    9600, 19200, 38400, 57600, 115200 Bd (default setting)

  • Stop bit

    Select a uniform data frame for all devices in the bus structure.

One stop bit (default setting)
Two stop bits

  • Parity
    Select a uniform data frame for all devices in the bus structure.

none
even
odd (default setting)

  • Modbus timeout

Modbus slave mode
Not configurable.

Modbus gateway mode
1 ... 450 ms
If you select a timeout outside of this time range, there will be an error message.


images/download/attachments/251039198/RS-485_%28Modbus_RTU%29-version-1-modificationdate-1636637458000-api-v2.png